Non-Interchangeable NIST Probes
NIST probes whose thread size and connection design vary by gas; they connect only to the matching medical gas outlet and prevent mix-ups between…
Kit used to remove particles and foreign matter from medical gas pipes and confirm that the line operates safely; 75 / 150 Lpm flow, HTM 02-01 compliant.
The 66.1138 kit is used when medical gas lines are being commissioned or taken in for maintenance. It serves to clean out particles and foreign matter left inside the pipes and then to verify that the system operates safely.
It is manufactured in accordance with HTM 02-01 and the related European standards. The kit operates at a flow rate of 75 / 150 Lpm; on the filtration side it includes a 47 mm hydrophobic membrane filter and filter papers with a pore size of 0.45 µm.
| Flow Rate | 75 / 150 Lpm |
|---|---|
| Membrane Filter | 47 mm hydrophobic |
| Filter Paper Pore Size | 0.45 µm |
| Compliant Standards | HTM 02-01 and related European standards |
For every device you purchase we set up an installation, training and after-sales support plan. Contact our teams for preventive maintenance contracts, spare parts and clinical application support.
NIST probes whose thread size and connection design vary by gas; they connect only to the matching medical gas outlet and prevent mix-ups between…
BS probes shaped separately for each gas type that fit only the matching medical gas outlet; they prevent incorrect connections and help improve…
Kit for testing and calibrating BS-type terminal units; includes two pressure guns, a vacuum gun and an impact-resistant case for field use.
Precision device developed for leak-tightness checks and pressure-loss measurement; used on gas and liquid lines, with a light body that is operated…
Test kit that verifies the vacuum and flow performance of operating theatre anaesthetic gas scavenging systems during commissioning and periodic…